Simple design combined with proper sizing of components makes this a highly durable and reliable generator.
MECHANICAL CONSTRUCTION
The stator and bearing shields are made of aluminum. The rotor shaft is made of C50 steel. Ventilation is provided by a fan on the rotor shaft. Enclosure class IP23 as standard; IP44 is available upon request. The generators are equipped with permanently lubricated bearings, type 6205 2RS at the front and 6203 2RS at the rear. The generators are delivered unpainted.
INSULATION
The generators are rated to insulation class H. All windings are impregnated with epoxy resin.
VOLTAGE REGULATION
The T-generators are regulated by a compound system and are equipped with brushes. Voltage accuracy is ±5 percent from no-load to full load with a power factor of 0.8–1 and a speed variation of 4 percent. The voltage can be adjusted by changing the air gap in the transformer. If the rated load is connected while the generator is running unloaded, the transient voltage drop is less than eight percent and the recovery time is less than 0.1 seconds. The control ensures that, regardless of speed, the magnetizing current can never reach a level that could be harmful.
OVERLOAD
The permitted overload is 380 percent for 20 seconds and 10 percent for one hour every six hours.
RADIO INTERFERENCE
The generators comply with VDE 0875 Class G and MIL-I-169-10A. Interference filters compliant with VDE Class K and MIL-STD-461-AB, as well as other standards, are available upon request.
OPTIONAL EQUIPMENT
The T16 and T20 generators are available in the desired voltages and with a built-in rectifier bridge for 12-volt battery charging.