Simple design combined with proper sizing of components makes this a highly durable and reliable generator.
MECHANICAL CONSTRUCTION
Stator and bearing shields are made of aluminum. Rotor shaft is in C50 steel. Ventilation by fan on the rotor shaft. Enclosure class IP23 as standard, IP44 available on request. The generators are equipped with disposable lubricated bearings type 6205 2RS front and 6203 2RS rear. The generators are delivered unpainted.
INSULATION
The generators are designed with insulation class H. All windings are impregnated with epoxy resin.
VOLTAGE REGULATION
T generators are regulated by a compound system and are equipped with brushes. The voltage accuracy is ± five percent from no load to full load with a power factor of 0.8-1 and a speed variation of four percent. The voltage can be adjusted by changing the air gap in the transformer. If the rated load is switched on when the generator is running at no load, the transient voltage drop is less than eight percent and the recovery time is less than 0.1 seconds. The regulation ensures that regardless of the speed, the magnetizing current can never reach a level that could be harmful.
OVERLOAD
Permissible overload is 380% for 20 seconds and 10% for one hour every six hours.
RADIO INTERFERENCE
The generators comply with VDE 0875 class G and MIL I 169-10A. Interference filters according to VDE class K and MIL STD 461-AB and other standards are available on request.
EXTRA EQUIPMENT
The T16 and T20 generators are available in the desired voltages and with a built-in rectifier bridge for 12-volt battery charging.